siliconups



Home








Contact Us








Inquiry
Our Mission
 
We give you the best solutions beyond your imagination.

 
 
Technical Specification For True Online...
 
  • UPS–GN-SERIES:

    Single Phase I/P Single Phase O/P

     

    Three Phase I/P Single Phase O/P

     

    Three Phase I/P Three Phase O/P

    PARAMETER

             SPECIFICATION

             SPECIFICATION

             SPECIFICATION

    INPUT

     

     

     

    Normal Voltage

    220V AC three Phase & N

    415V AC three Phase & N

    415V AC three Phase & N

    Input Voltage Window

    ( + 25% )

    ( + 25% )

    ( + 25% )

    Normal Frequency

    50 Hz + 6%

    50 Hz + 6%

    50 Hz + 6%

    DC BUS

    48V – 192VDC

    120VDC  - 360VDC

    120 - 360VDC

    RECTIFIER

    Full wave.

    Full wave.

    Full wave.

    CHARGER

    Active Input Power Factor Correction.

    Active Input Power Factor Correction.

    Active Input Power Factor Correction.

    INPUT PF

    >.99

    >.99

    >.99

    INPUT CURRENT THD.

    <5%

    <5%

    <5%

    Type

    CVCC

    CVCC

    CVCC

    Nominal Voltage Regulation

    ( + )  1%

    ( + )  1%

    ( + )  1%

    Ripple
    (without battery)

    < 1%

    < 1%

    < 1%

    OUTPUT

     

     

     

    Power factor

    Unity as per IEC 62040-3
    (performance standards)

    Unity as per IEC 62040-3
    (performance standards)

    Unity as per IEC 62040-3
    (as per performance standards)

    Nominal Voltage

    220VAC Single phase.

    220VAC Single phase.

    400VAC, 3Phase-3Phase with N,
    220VAC Single phase between L & N

    Regulation

    ( + )  1%

    ( + )  1%

    ( + )  1%

    Frequency

    50Hz + 0.1 Hz

    50Hz + 0.1 Hz

    50Hz + 0.1 Hz

    Waveform

    True sine wave

    True sine wave

    True sine wave

    ISOLATION

    True Online with complete galvanic isolation as per IEC 62040-1
     (saftey standards)

    True Online with complete galvanic isolation as per IEC 62040-1 (saftey standards)

    True Online with complete galvanic isolation as per IEC 62040-1 (saftey standards)

    Total Harmonic Distortion

    <2% Minimum for linear load,
    5% for non linear load

    <2% Minimum for linear load,
    5% for non linear load

    <2% Minimum for linear load,
    5% for non linear load

    Overload Capacity

    125% for 10 mins,
    150% for 1Sec

    125% for 10 mins,
    150% for 1Sec

    125% for 10 mins,
    150% for 1Sec

    Invertor Type

    IGBT based PWM with Instantaneous Sine Wave Control

    IGBT based PWM with Instantaneous Sine Wave Control

    IGBT based PWM with Instantaneous Sine Wave Control

    Transient Response

    Remain within +1 % & recover to 100% within one ¼ cycle

    Remain within +1 % & recover to 100% within one ¼ cycle

    Remain within +1 % & recover to 100%
    within one ¼ cycle

    Crest Factor

    3:1

    3:1

    3:1

    Duty

    Continuous

    Continuous

    Continuous

    Manual Bypass

    Provided

    Provided

    Provided

    EFFICIENCY

     

     

     

    Invertor Efficiency
    ( DC to AC )

    >93%

    >93%

    >93%

    Converter Efficiency

    >94%

     

    >94%

    >94%

    Overall Efficiency

    >87%

     

    >87%

    >87%

    PROTECTIONS:
    CONVERTOR PROTECTION : Advanced Electronic Protection for device safety backed up with MCB’s/ MCCBs & fast acting fuses.  Soft start for 0-20 seconds power walk-in. 
    INVERTOR PROTECTION   : Advanced Electronic Protection for device safety backed up with MCB’s/ MCCBs & fast acting fuses, high speed pulse by pulse electronic over voltage / under voltage protection, Electronic over current trip with reset.

     

    PROTECTIONS:
    CONVERTOR PROTECTION : Advanced Electronic Protection for device safety backed up with MCB’s/ MCCBs & fast acting fuses.  Soft start for 0-20 seconds power walk-in. 
    INVERTOR PROTECTION   : Advanced Electronic Protection for device safety backed up with MCB’s/ MCCBs & fast acting fuses, high speed pulse by pulse electronic over voltage / under voltage protection, Electronic over current trip with reset.

    PROTECTIONS:
    CONVERTOR PROTECTION : Advanced Electronic Protection for device safety backed up with MCB’s/ MCCBs & fast acting fuses.  Soft start for 0-20 seconds power walk-in. 
    INVERTOR PROTECTION   : Advanced Electronic Protection for device safety backed up with MCB’s/ MCCBs & fast acting fuses, high speed pulse by pulse electronic over voltage / under voltage protection, Electronic over current trip with reset.